Command Description
%AANNTTCCFF Set Module Configuration
$AA0Ci Perform Analog Input Channel Zero Calibration
$AA1Ci Perform Analog Input Channel Span Calibration
$AA2 Read Configuration
$AA3 Read Channel Enable/Disable Status
$AA4 Read Analog Input Synchronized Data
$AA5 Read Reset Status
$AA5VV Set channel enable/disable status
$AA6 Read Excitation Voltage Value
$AA7CiRrr Set Single Channel Range Configuration
$AA7(Data) Set Excitation Voltage Output Value/td>
$AA8Ci Read Single Channel Range Configuration
$AAA Perform Excitation Voltage Zero Calibration
$AAB Perform Excitation Voltage Span Calibration
$AAEVV Trim Excitation Voltage Output
$AAF Read firmware version
$AAI read INIT Status
$AAM Read module name
$AAS Set Excitation Voltage As Power-On Value
$AAS(Data) Set Data As Excitation Voltage Output Power-On Value
$AAS1 Reload Default Calibration Prarameter
#** Synchronized Sampling
#AA Read analog inputs of all channels
#AAN Read analog input of specificed channel
@AA6Ci Read Lower And Upper Source Limits of Linear Mapping
@AA6Ci(SL)(SH) Set Lower and Upper Source Limits of Linear Mapping
@AA7Ci Read Lower And Upper Target Limits of Linear Mapping
@AA7Ci(TL)(TH) Set Lower and Upper Target Limits of Linear Mapping
@AAA Read Linear Mapping Enable/Disable Status
@AAAV Set Linear Mapping Enable/Disable
@AACA Clear Latched Alarm *
@AACECi Clear Event Counter
@AADA Disable Alarm *
@AADI Read Alarm Status, DO Status and DI Status
@AADO(Data) Set Digital Output Status
@AAEAT Enable Latched/Momentary Alarm *
@AAHI(Data) Set Hight Alarm Limit *
@AALO(Data) Set Low Alarm Limit *
@AARECi Read Event Counter
@AARH Read High Alarm Limit *
@AARL Read Low Alarm Limit *
~** Host Watchdog OK signal
~AA0 Read Host Watchdog Status
~AA1 Reset Host Watchdog Timeout Status
~AA2 Read Host Watchdog Setting
~AA3ETT Set host watchdog timeout setting
~AA4 Read DO Power-On and Safe Value
~AA5PPSS Set DO Power-On and Safe Value
~AAD Read Misc Setting, bit 4 is Sampling Rate
~AADVV Set Misc Setting
~AAEV Enable/Disable Analog Input Calibration
~AAI Soft INIT
~AAO(Name) Set module name
~AAHB Read Half-Bridge Configuration
~AAHBVV Set Half-Bridge Configuration
~AAZOCi Read Zero Offset of Channel i
~AAZOCi(Data) Set Zero Offset of Channel i
 Note: *   Alarm function is only for Analog Input Channel 0



Back to Previous Page