Command |
$AAS(Data) |
Description |
Set excitation voltage value as power-on value |
Syntax |
$AAF(Data)[CHK](cr)
$ |
a delimiter character |
AA |
address of reading module (00 to FF) |
S |
command for setting excitation voltage value
|
(Data)
|
engineer unit format, +00.000 ~ +10.000
|
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AA[CHK](cr) |
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command. |
AA |
address of response module (00 to FF) |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
$01S+05.123 |
Response |
!01 |
Description |
Set address 01 excitation voltage value +05.123, and return success.
|
|
|