Command $AAS(Data)
Description Set excitation voltage value as power-on value
Syntax $AAF(Data)[CHK](cr)
$ a delimiter character
AA address of reading module (00 to FF)
S command for setting excitation voltage value
(Data)
engineer unit format, +00.000 ~ +10.000
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S+05.123
Response !01
Description Set address 01 excitation voltage value +05.123, and return success.