Command $AA1L
Description Read Non-isolated Low Trigger Level
Syntax $AA1L(data)[CHK](cr)
$ a delimiter character
AA address of setting module (00 to FF)
1L command for reading non-isolated low trigger level
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA(data)[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
(data) low trigger level in 0.1V unit.
The data is from 01 to 50 to present trigger level from 0.1V to 5.0V
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $011L
Response !0108
Description Read address 01 non-isolated low trigger level, return trigger level 0.8V

Reference $AA1H
$AA1H(data)
$AA1L(data)



Back to Previous Page