Command |
$AASiCjM(Data) |
Description |
Set Maximum Counter Value for certain channel |
Syntax |
$AASiCjM(Data)[CHK](cr)
$ |
a delimiter character |
AA |
address of setting module (00 to FF) |
Si |
slot number of the module. i = 0 ~ 3 or 0 ~ 7 |
Cj |
j = 0
=
read maximum counter value of counter 0
j = 1 = read
maximum counter value of counter 1 |
M |
command for setting maximum counter value |
(Data) |
8 hexdecimal digits, from 00000000 to FFFFFFFF. |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of
command |
|
Response |
Valid
Command |
!AA[CHK](cr) |
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command. |
AA |
address of response module (00 to FF) |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of
response |
|
Example |
Command |
$01S1C0MFFFFFFFF |
Response |
!01 |
Description |
Set address 01,slot 1 counter/frequency module's
maximum counter value of counter 0
to 4294967295, return success. |
|
Modules |
I-87082 on I-8000 slave I/O unit |
Reference |
$AASiCjM
|
|