Command $AASiCjM
Description Read Maximum Counter Value  for certain channel
Syntax $AASiCjM[CHK](cr)
$ a delimiter character
AA address of reading module (00 to FF)
Si slot number of the module. i = 0 ~ 3 or 0 ~ 7
Cj j = 0 = read maximum counter value of counter 0
j = 1 = read maximum counter value of counter 1
M command for reading maximum counter value
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA(data)[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
(Data) 8 hexdecimal digits, from 00000000 to FFFFFFFF
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S1C0M
Response !01FFFFFFFF
Description Read address 01,slot 1 counter/frequency module's maximum counter value of counter 0, return value 4294967295.
Modules I-87082 on I-8000 slave I/O unit
Reference $AASiCjM(Data)