Command ~AADT
Description Set the temperature scale
Syntax ~AADT[CHK](cr)
~ a delimiter character
AA address of reading module (00 to FF)
D
command for setting  temperature scale
T
temperature scaling
0 = Celsius.
1 = Fahrenheit.
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command ~01D0
Response !010
Description Set temperature scale of module is Celsius, response success.



Back to Previous Page