Format Selection
Analog Input Module I-87013, I-87015, I-87015T, I-87017, I-87017R
, I-87017RC, I-87017ML, I-87018, I-87018R, I-87019R
Analog Output Module I-87022, I-87026, I-87024
Digital Input/Output Module I-8704x/5x/6x
Counter/Frequency Input Module I-87082

Back to Previous Page


Format Table for Analog Input Module
Bit Location 7 6 5 4 3 2 1 0
Description Filter Selection CheckSum Selection Mode Setting Reserved Data Format Selection

 Filter Selection  0 = 60Hz rejection This setting is reserved for the I-87015, I-87015T and I-87019R, it should be zero.
 1 = 50Hz rejection 
 CheckSum Selection  0 = CheckSum disable
 1 = CheckSum enable
 Mode Setting
(Only available for I-87017R,
I-87017RC and I-87017ML)
 0 = Normal mode : 10 samples/sec, 16-bits
 1 = Fast mode      : 60 samples/sec, 12-bits
 Data Format Selection  00 = Engineer Unit Format
 01 = % of FSR Format
 10 = 2's Complement Hexadecimal Format
 11 = Ohms in Engineer Unit Format For I-87013 Only

Example
Format CodeDescription
0060Hz rejection, CheckSum disabled, engineer unit format
4160Hz rejection, CheckSum enabled, % of FSR format
82 50Hz rejection, CheckSum disabled, 2's complement hexadecimal format

Back to Previous Page

Format Table for Analog Output Module
Bit Location 7 6 5 4 3 2 1 0
Description Not Used CheckSum Selection Slew Rate Control Data Format Selection

 CheckSum Selection  0 = CheckSum disable
 1 = CheckSum enable
 Slew Rate Control
( For 87022/26 )
 Set to 0.
 Slew Rate Control
( For 87024 )
 0000 = Immediate output
 0001 = 0.0625V/Second or 0.125mA/Second
 0010 = 0.125V/Second or 0.25mA/Second
 0011 = 0.25V/Second or 0.5mA/Second
 0100 = 0.5V/Second or 1.0mA/Second
 0101 = 1.0V/Second or 2.0mA/Second
 0110 = 2.0V/Second or 4.0mA/Second
 0111 = 4.0V/Second or 8.0mA/Second
 1000 = 8.0V/Second or 16.0mA/Second
 1001 = 16.0V/Second or 32.0mA/Second
 1010 = 32.0V/Second or 64.0mA/Second
 1011 = 64.0V/Second or 128.0mA/Second
 1100 = 128.0V/Second or 256.0mA/Second
 1101 = 256.0V/Second or 512.0mA/Second
 1110 = 512.0V/Second or 1024.0mA/Second
 1111 = 1024.0V/Second or 2048.0mA/Second
 Data Format Selection  00 = Engineer Unit Format

Example
Format CodeDescription
00CheckSum disabled, immediate output, engineer unit format
44CheckSum enabled, 0.0625V/Second or 0.125mA/Second output slew rate, engineer unit format
10CheckSum disabled, 0.5V/Second or 0.25mA/Second output slew rate, engineer unit format

Back to Previous Page


Format Table for Digital Input/Output Module
Bit Location 7 6 5 4 3 2 1 0
Description Counter Updated Direction CheckSum Selection Not Used Not Used Not Used Not Used Not Used Not Used

 CheckSum Selection  0 = CheckSum disable
 1 = CheckSum enable
Counter Updated Direction  0 = Falling edge
 1 = Rising edge



Format Table for Counter/Frequency Input Module
Bit Location 7 6 5 4 3 2 1 0
Description Not Used CheckSum Selection Not Used Not Used Not Used Frequency Gate Time Not Used Not Used

 CheckSum Selection  0 = CheckSum disable
 1 = CheckSum enable
 Frequency Gate Time  0 = 0.1 Second
 1 = 1.0 Second



Back to Previous Page