Command |
~AA5S |
Description |
Set PowerOn Value / Safe Value |
Syntax |
~AA5S[CHK](cr)
~ |
a delimiter character |
AA |
address of setting module (00 to FF) |
5 |
command for store current output as PowerOn Value / Safe Value
|
S |
P = Set PowerOn Value
S = Set Safe Value |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AA[CHK](cr) |
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command. |
AA |
address of response module (00 to FF) |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
~015P |
Response |
!01 |
Description |
Set PowerOn Value of address 01, response success. |
|
Reference |
~AA4S
|
|