Command $AA9N
Description Readback current output value of specificed output channel
Syntax $AA9N[CHK](cr)
$ a delimiter character
AA address of reading module (00 to FF)
9 command for read DA configuration of channel N
N specificed channel for read current output value
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AATS[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
T analog output type.
S analog output slewrate.
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $0190
Response !0110
Description Read DA configuration of channel 0 of address 01 , return 4 to 20mA output and change imediate.
Reference $AA9NTS