Command $AA1N
Description I-87022/26/24C/28C :
Perform 20mA calibration for specificed output channel
I-87024 :
Perform 20mA/+10V calibration for specificed output channel
Syntax $AA1N[CHK](cr)
$ a delimiter character
AA Address of setting module (00 to FF)
1 Command for performing calibration
For I-87024 :
Type = 30, perform 20mA calibration
Type = 32, perform +10V calibration.
N Specificed channel for calibration
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command.
AA address of response module (00 to FF)
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $0111
Response !01
Description I-8722/26 :
Perform 20mA calibation of channel 1 of address 01, response success.
I-87-24 :
Perform 20mA(or +10V) calibation of channel 1 of address 01, response success.
Reference $AA0N



Back to Previous Page