Analog Input | Input Channel | 7 RTD Input Channels |
Input Type | 2-Wire or 3-Wire RTD | |
RTD Range | Pt100, Pt1000, Ni120 Cu100, Cu1000 |
|
Sampling Rate | 10 samples/second total | |
-3dB BandWidth | 5.24Hz | |
Accuracy | +/-0.05% | |
Common Mode Rejection | 100dB @50/60Hz | |
Normal Mode Rejection | 100dB @50/60Hz | |
Isolation Voltage | 3000Vdc | |
LED Display |
1 LED as Power/Communication indicator 7 LEDs as High/Low Alarm signals |
|
Power Consumption | Maximum :1.0W |
Configuration | Default Setting | Description |
---|---|---|
Address | 01 | Module Address = 01 |
Type | 20 | PT100, a=0.00385, -100 to 100 degree Celsius |
Baudrate | 0A | 115200 bps |
Format | 00 | 60Hz rejection CheckSum disable Engineer Unit Format |