2012/01/17 by Andy Firmware: v1.04 => v1.05 1. Swap modbus AI/AO data bytes, (FC 0x03, 0x04, 0x10), for ethernet/ip input/output data. 2. Change MAC adress from 90:xx:xx ~ 91:xx:xx to 80:xx:xx ~ 8F:xx:xx ===================================== 2011/11/18 by Andy Firmware: v1.03 => v1.04 1. Add arp request function to gateway at initial status. 2. ForwardOpen O=>T connection method need to add RUN_IDLE_HEADER 3. modify eip socket timeout value from 10s to 30s 4. fix bug of MAC address error 5. fix bug of EIP TCP keepalive ack timeout Utility: v1.02 => v1.03 1. For Diagnostic methhod => Add RUN_IDLE_HEADER for ForwardOpen O=>T connection, used for FW v1.04 or later ===================================== 2011/09/16 by Andy Utility: v1.01 => v1.02 1. fix the bug of creating wrong EDS file ===================================== 2011/08/04 by Andy Firmware: v1.02 => v1.03 1. Remove 03B IC checking function ===================================== 2010/12/31 by Andy Firmware: v1.01 => v1.02 1. fix the MAC address range bug on boot loader and firmware 00:0D:E0:8F:xx:xx => 00:0D:E0:90:xx:xx 2. fix the bug of the E2MB_SERIALNUMBER 3. fix the bug of Modbus 3.5T timer 4. add class 0x04 instance 0x67 for Modbus command status ===================================== 2010/11/16 by Andy Firmware: v1.01 EtherNet/IP Features: * Ethernet Protocol: EtherNet/IP Server * Maximum number of Explicit Messaging connections: 6 * Supported I/O connection methods: .Transport and trigger: Exclusive-Owner, Cyclic .Original to Target Type: POINT2POINT .Target to Original Type: POINT2POINT, MULTICAST * Device Configuration Option: Custom Software * Address Configuration: DHCP, Custom Software * Maximum EtherNet/IP Input/Output data size: 500 bytes * Maximum Modbus RTU slave data mapped to EtherNet/IP input data: 500 bytes * Maximum EtherNet/IP output data mapped to Modbus RTU slave devices: 500 bytes Modbus Features: * Modbus Protocol: Modbus RTU Master * Maximum support 30 Modbus RTU slave devices * Supported Modbus RTU Function Codes: .01 hex: Read Output Status .02 hex: Read Input Status .03 hex: Read Multiple Data Registers .04 hex: Read Input Registers .0F hex: Write Multiple Bits .10 hex: Write Multiple Data Register * Maximum data size per Modbus slave device: 240 bytes