| Command |
~AA5N |
| Description |
Set Safe Value of specified output channel |
| Syntax |
~AA5N[CHK](cr)
| ~ |
a delimiter character |
| AA |
address of setting module (00 to FF) |
| 5 |
command for set current output value as Safe Value
|
| N |
specified channel for set Safe Value |
| [CHK] |
2 characters of Checksum |
| (cr) |
Character Return(0x0D) for denote the end of command |
|
| Response |
| Valid Command |
!AA[CHK](cr) |
| Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
| ! |
delimiter for valid command |
| ? |
delimiter for invalid command. |
| AA |
address of response module (00 to FF) |
| [CHK] |
2 characters of Checksum |
| (cr) |
Character Return(0x0D) for denote the end of response |
|
| Example |
| Command |
~0152 |
| Response |
!01 |
| Description |
Set current output value as Safe Value of channel 2 of address 01, response success. |
|
| Reference |
#AAN(Data)
~AA4N
|
|