Command |
$AA4 |
Description |
Read Digital Filter Status |
Syntax |
$AA4[CHK](cr)
$ |
a delimiter character |
AA |
address of reading module (00 to FF) |
4 |
command for reading digital filter enabled/disabled status. |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AAS[CHK](cr) |
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command. |
AA |
address of response module (00 to FF) |
S |
digital filter status
1 = disable filter.
0 = enable filter. |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
$014 |
Response |
!011 |
Description |
Read address 01 digital filter status, return the digital fileter is enabled. |
|
Reference |
$AA4S
|
|