Copyright March 2002 by ICP DAS CO., LTD. All right reserved. Trademark: Products, names and trade names appeared belongs to their respective owner. This document describe the way to free the COM1 of uPAC-7186EG controller. 1. Create a file folder named "7186EG" in your hard drive. For example, "c:\7186EG". 2. Copy \Napdos\ISaGRAF\7186EG\Driver\1.01\"7188xw.exe", "7188xw.ini", "7188xw.f4", "isa7186e.exe", "autoexec.bat" & "86-07131.IMG" from the CD_ROM into your "7186EG" folder. 3. Run "\7186EG\7188xw.exe" in your hard drive. A "7188xw" screen will appear. 4. Link COM1 or COM2 of your PC to COM1 of the uPAC-7186EG controller through a RS232 cable. 5. Power off the uPAC-7186EG controller, connect pin "INIT" to "GND" and then power it up. 6. If the connection is Ok, messages will appear on the 7188xw screen. ICP_DAS MiniOS7_UDP for I-7186Ex Ver. 2.02 build 011,Oct 31 2007 13:54:46 OS id=31 SRAM:640K, FLASH MEMORY:512K [CPU=R2240] CPU internal WDT is ENABLE(WDT timeout=0.8 sec) Serial number= 5A 5A 5A 5A 5A 5A 5A 5A i7186EX_UDP> 7. Type "isa7186e *f=1" to free the COM1 of uPAC-7186EG. i7186EX_UDP> isa7186e *f=1 Com1 is free now 8. Type "isa7186e *f=0" to define the COM1 of uPAC-7186EG for Modbus RTU . i7186EX_UDP> isa7186e *f=0 Com1 is define as Modbus RTU Set Com1 Baudrate to xxxxxx 9. Press ALT_X to exit "7188xw". 10. Remove the connection between "INIT*" - "GND", reset the uPAC-7186EG.