Command |
#AASiCj |
Descrpition |
Read the RTD input module data from specified slot and channel in
the I-8000 system. The data format is engineering units only. |
Syntax |
#AASiCj[CHK](cr)
# |
a delimiter character |
AA |
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh |
Si |
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots) |
Cj |
specified channel number. j = 0 to 3 |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!(data)[chk](cr)
|
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command |
(data) |
Return from RTD input module in engineering. |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Exapmle |
Command |
#01S3C0 |
Response |
!+22.34(cr) |
Description |
The data read from the RTD module in slot 3 and
channel 0 of the I-8000 system at address 01h is +22.34 C deg. |
|
|
|
Modules |
I-87013
|
|