Command #AASiCj
Descrpition Read the RTD input module data from specified slot and channel in the I-8000 system. The data format is engineering units only.
Syntax #AASiCj[CHK](cr)
# a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number. j = 0 to 3
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !(data)[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
(data) Return from RTD input module in engineering.
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Exapmle
Command #01S3C0
Response !+22.34(cr)
Description The data read from the RTD module in slot 3 and channel 0 of the I-8000 system at address 01h is +22.34 C deg.


Modules I-87013