This command to clear the Digital Input counter
value from the specified channel of Digital I/O module with digital
input channel.
This command only applies on all 87K digital I/O modules with digital
input channel which are plugged
in the specified Slot of the I-8000 system.
Syntax
$AASiCjj[CHK](cr)
$
a delimiter character
AA
address number of the I-8000 system. AA= 00 ~ FFh
Si
slot number of the module. i = 0 ~ 3 or 0 ~ 7
C
Command for Channel
jj
jj: 00 ~ 0F if channel count<=16; jj: 0 ~ 1F for 32
channel count
Character Return(0x0D) for denote the end of the response
Example
Command
$01S1C02
Response
!01
Description
The example clear the digital input module's DI counter value
from slot 1 of the I-8000 system at address 01h.After using this