Command
~AASi5PC
Description
Disables power on value of DO or DIO module in specific slot of the I-8000 system.
Syntax
~AASi5PC[CHK](cr)
~ a delimiter character
AA address number of the I-8000 system. AA= 00 ~ FFh
Si slot number of the module. i = 0 ~ 3 or 0 ~ 7
5PC command to disable power on value
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of the command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA address number of the I-8000 system
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of the response
Example
Command ~01S75PC
Response !01(cr)
Description Disables power on value of DO or DIO module in slot7 of the I-8000 system (address=01h).
 