Command
~AASi5P
Description
Enables power on value of DO or DIO module in specific slot of the I-8000 system. The current DO status is set to power on value.
Syntax
~AASi5P[CHK](cr)
~ a delimiter character
AA address number of the I-8000 system. AA= 00 ~ FFh
Si slot number of the module. i = 0 ~ 3 or 0 ~ 7
5P command to set and enable power on value
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of the command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA address number of the I-8000 system.
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of the response
Example
Command ~01S75P
Response !01(cr)
Description Enables power on value of DO or DIO module in slot7 of the I-8000 system (address=01h) and set the current DO status as power on value.
 
Modules
DO or DIO modules