Command %AANNCCFF
Description This command set the specified I-8000 system baud rate and checksum status.
If set the address to 0.It will set the system configuration into initial state.In this state the baud rate is 9600 and check sum is disable.
Syntax %AANNCCFF[CHK](cr)
% a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
NN It is reserved for future application. It should be 00h.
CC Baudrate code Baudrate
FF Data format code Format
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command %01000A40
Response !01(cr)
Description The example to configure the I-8000 system at address 01h.
Baudrate = > 115.2K bps
Check sum => enabled
The response indicates the command is valid.
Note Remember to connect the INIT terminal to the ground before you change the Baud rate and checksum status. When finished the step then release the INIT pin and restart power.


Modules I-8410,I-8810,I-8430,I-8431,I-8830,I-8831,I-8KE4,I-8KE8