This command set the specified I-8000 system baud rate and
checksum status.
If set the address to 0.It will set the system
configuration into initial state.In this state the baud rate is 9600
and check sum is disable.
Syntax
%AANNCCFF[CHK](cr)
%
a delimiter character
AA
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh
NN
It is reserved for future application. It should be 00h.
Character Return(0x0D) for denote the end of response
Example
Command
%01000A40
Response
!01(cr)
Description
The example to configure the I-8000 system at address 01h.
Baudrate = > 115.2K bps
Check sum => enabled
The response indicates the command is valid.
Note
Remember to connect the INIT terminal to the ground before
you change the Baud rate and checksum status. When finished
the step then release the INIT pin and restart power.