Command $AASiCjB
Description Read the Analog Data Output module configuration from the specified Slot and channel in the I-8000 system.
Syntax $AASiCjB[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number. j = 0 to 3
B command for read Analog data output module configuration
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AARRFF[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
RR Input range code Type
FF Data format code Format
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S1C0B
Response !013300(cr)
Description The Analog Data output Module in slot 1 of the I-8000 system at address 01h ,that a output range +/-10V, data format is engineering unit, slew rate is immediate change.


Modules I-87024,I8024



Back to Previous Page