Note:These Command Just for Slave
I-8000 Series(I-8410,I-8810)
Command
$AASiCjB
Description
Read the Analog Data Output module configuration from the
specified Slot and channel in the I-8000 system.
Syntax
$AASiCjB[CHK](cr)
$
a delimiter character
AA
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh
Si
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots)
Cj
specified channel number. j = 0 to 3
B
command for read Analog data output module configuration
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of command
Response
Valid Command
!AARRFF[chk](cr)
Invalid Command
?AA[CHK](cr)
Syntax error or communication error may get no response.
!
delimiter for valid command
?
delimiter for invalid command
AA
2-characters HEX module address
RR
Input range code Type
FF
Data format code Format
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of response
Example
Command
$01S1C0B
Response
!013300(cr)
Description
The Analog Data output Module in slot 1 of the I-8000 system
at address 01h ,that a output range +/-10V, data format
is engineering unit, slew rate is immediate change.
Modules
I-87024,I8024