Note:These Command Just for Slave
I-8000 Series(I-8410,I-8810)
Command
$AASiCjARRFF
Description
This command set the analog data output module that output range,
data format and slew rate for the specified channel and slot
in the I-8000 system.
Syntax
$AASiCjARRFF[CHK](cr)
$
a delimiter character
AA
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh
Si
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots)
Cj
specified channel number. j = 0 to 3
A
Command for set the output range, data format of the analog output module
RR
Input range code Type
FF
Data format code Format
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of command
Response
Valid Command
!AA[chk](cr)
Invalid Command
?AA[CHK](cr)
Syntax error or communication error may get no response.
!
delimiter for valid command
?
delimiter for invalid command
AA
2-characters HEX module address
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of response
Example
Command
$01S0C1A3300
Response
!01(cr)
Description
This example set the channel 2,slot 0 in the I-8000 system
at address 01h with +/-10V output range, immediate change and
engineering unit data format. The response indicates the
command is valid.
Modules
I-87024,I-8024