Command $AASiCj4
Description This command set the Analog Data Output module Start up configuration for the specified Slot and channel in the I-8000 system.
Syntax $AASiCj4[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number. j = 0 to 3
4 command for Set start up configuration
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S1C04
Response !01(cr)
Description The Analog Data output Module in slot 1 of the I-8000 system at address 01h that set the last value for the start up configuration.


Modules I-87024,I8024



Back to Previous Page