Command |
$AASiCj4 |
Description |
This command set the Analog Data Output module Start up configuration
for the specified Slot and channel in the I-8000 system. |
Syntax |
$AASiCj4[CHK](cr)
$ |
a delimiter character |
AA |
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh |
Si |
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots) |
Cj |
specified channel number. j = 0 to 3 |
4 |
command for Set start up configuration |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AA[chk](cr)
|
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command |
AA |
2-characters HEX module address |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
$01S1C04 |
Response |
!01(cr) |
Description |
The Analog Data output Module in slot 1 of the I-8000 system
at address 01h that set the last value for the start up
configuration. |
|
|
|
Modules |
I-87024,I8024
|
|