Command $AASiCj1
Description This command to implement the Analog Data output module 20mA calibration in the specified Slot and channel of the I-8000 system.
Syntax $AASiCj1[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number. j = 0 to 3
1 command for zero calibration
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Note:
Do not use this command until you really understand this command.
Before use this calibration command,You must trim the correct value use trim calibration command.refer to Trim command


Example
Command $01S21
Response !01(cr)
Description The response indicates the command is valid.


Modules I-87024,I-8024



Back to Previous Page