Note:These Command Just for Slave
I-8000 Series(I-8410,I-8810)
Command
$AASiCj1
Description
This command to implement the Analog Data output module 20mA
calibration in the specified Slot and channel of the I-8000 system.
Syntax
$AASiCj1[CHK](cr)
$
a delimiter character
AA
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh
Si
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots)
Cj
specified channel number. j = 0 to 3
1
command for zero calibration
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of command
Response
Valid Command
!AA[chk](cr)
Invalid Command
?AA[CHK](cr)
Syntax error or communication error may get no response.
!
delimiter for valid command
?
delimiter for invalid command
AA
2-characters HEX module address
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of response
Note:
Do not use this command until you really understand this command.
Before use this calibration command,You must trim the correct value
use trim calibration command.refer to Trim command
Example
Command
$01S21
Response
!01(cr)
Description
The response indicates the command is valid.
Modules
I-87024,I-8024