Command $AASiCj0
Description Implement the analog output module 0mA calibration in the specified slot and channel of the I-8000 system.
Syntax $AASiCj0[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number. j = 0 to 3
0 command for span calibration
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Note:
Do not use this command until you really understand this command.
Before use this calibration command,You must trim the correct value use trim calibration command.refer to Trim command


Example
Command $01S1C20
Response !01(cr)
Description This command implement 0mA calibration in the slot1 and channel 2 of the I-8000 system at address 01h.The response indicates the command is valid.


Modules I-87024,I-8024