Command $AASiCjRHC
Description Read the specified analog input channel and slot High/Low alarm connection in the I-8000 system.
Syntax $AASiCjRHC[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number.
R Command for Read Alarm Function
H High/Low alarm, H = High alarm, L = Low alarm
C The connection of Alarm
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AASkCn[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
Sk Specified the slot number of digital output module.
k = 0 to 3(4 slots) or k = 0 to 7(8 slots)
Cn Specified the channel number of digital output module.
n = 0 to F
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S3C0RLC
Response !01S0C5
Description The low alarm connection for the analog input channel 0, slot 3 is setting with channel 5, slot 0 in the I-8000 system at address 01h.

Modules I-87013, I-87016, I-8017H, I-87017, I-87018



Back to Previous Page