Command |
$AASiCjRHC |
Description |
Read the specified analog input channel and slot High/Low alarm
connection in the I-8000 system. |
Syntax |
$AASiCjRHC[CHK](cr)
$ |
a delimiter character |
AA |
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh |
Si |
Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots) |
Cj |
specified channel number. |
R |
Command for Read Alarm Function |
H |
High/Low alarm, H = High alarm, L = Low alarm |
C |
The connection of Alarm |
[CHK] |
2 characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AASkCn[CHK](cr) |
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command |
AA |
2-characters HEX module address |
Sk |
Specified the slot number of digital output module.
k = 0 to 3(4 slots) or k = 0 to 7(8 slots) |
Cn |
Specified the channel number of digital output module.
n = 0 to F |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
$01S3C0RLC |
Response |
!01S0C5 |
Description |
The low alarm connection for the analog input channel 0,
slot 3 is setting with channel 5, slot 0 in the I-8000 system
at address 01h. |
|
|
Modules |
I-87013, I-87016, I-8017H, I-87017, I-87018
|
|