Command $AASiCjAHU(data)
Description This command set the specified channel and slot with High/Low Alarm Limit in the I-8000 system.
Syntax $AASiCjAHU(data)[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number.
A Command for Alarm Function
H High/Low alarm, H = High alarm, L = Low alarm
U command for set alarm limit value
(data) Alarm limit by engineering unit
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S3C0ALU+001.00
Response !01
Description This example set the channel 0,slot 3 low alarm limit with +1 C deg in the I-8000 system at address 01h
The response indicates the command is valid.

Modules I-87013, I-87016, I-8017H, I-87017, I-87018