Note:These Command Just for Slave
I-8000 Series(I-8410,I-8810)
Command
$AASiCjAHCSkCn
Description
This command set the specified channel and slot input High/Low Alarm
to the specified digital output channel and slot in the I-8000 system.
Syntax
$AASiCjAHCSkCn[CHK](cr)
$
a delimiter character
AA
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh
Si
Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj
specified channel number.
A
Command for Alarm Function
H
High/Low alarm, H = High alarm, L = Low alarm
C
The connection of Alarm
Sk
Specified the slot number of digital output module.
k = 0 to 3(4 slots) or k = 0 to 7(8 slots)
Cn
Specified the channel number of digital output module.
n = 0 to F
[CHK]
2 characters of Checksum
(cr)
Character Return(0x0D) for denote the end of command
Response
Valid Command
!AA[CHK](cr)
Invalid Command
?AA[CHK](cr)
Syntax error or communication error may get no response.
!
delimiter for valid command
?
delimiter for invalid command
AA
2-characters HEX module address
[CHK]
2-characters of Checksum
(cr)
Character Return(0x0D) for denote the end of response
Example
Command
$01S3C0CLCS0C5
Response
!01
Description
When slot 3, channel 0 Analog input occurred low alarm then
set the slot 0, channel 5 digital output in the I-8000 at
address 01h.
The response indicates the command is valid.
Modules
I-87013, I-87016, I-8017H, I-87017, I-87018