Command $AASiCjAHCSkCn
Description This command set the specified channel and slot input High/Low Alarm to the specified digital output channel and slot in the I-8000 system.
Syntax $AASiCjAHCSkCn[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj specified channel number.
A Command for Alarm Function
H High/Low alarm, H = High alarm, L = Low alarm
C The connection of Alarm
Sk Specified the slot number of digital output module.
k = 0 to 3(4 slots) or k = 0 to 7(8 slots)
Cn Specified the channel number of digital output module.
n = 0 to F
[CHK] 2 characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[CHK](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S3C0CLCS0C5
Response !01
Description When slot 3, channel 0 Analog input occurred low alarm then set the slot 0, channel 5 digital output in the I-8000 at address 01h.
The response indicates the command is valid.

Modules I-87013, I-87016, I-8017H, I-87017, I-87018



Back to Previous Page