Command |
$AASiB |
Description |
Read the analog input module
configuration from the specified Slot in the I-8000 system. |
Syntax |
$AASiB[CHK](cr)
$ |
a delimiter character |
AA |
2-characters HEX module address for the specified I-8000 system
,Range from 01 to FFh |
Si |
Specified slot number. i = 0 to 3(4 slots) or i = 0 to 7(8 slots) |
B |
Command for read RTD input range, data format |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of command |
|
Response |
Valid Command |
!AARRFF[chk](cr)
|
Invalid Command |
?AA[CHK](cr) |
Syntax error or communication error may get no response.
! |
delimiter for valid command |
? |
delimiter for invalid command |
AA |
2-characters HEX module address |
RR |
Input range code Type |
FF |
Data format code Format |
[CHK] |
2-characters of Checksum |
(cr) |
Character Return(0x0D) for denote the end of response |
|
Example |
Command |
$01S1B |
Response |
!012000(cr) |
Description |
The analog input Module in slot 1 of the I-8000 system
at address 01h that configuration is +/-15mV input range and
engineering unit data format. |
|
|
|
|