Command $AASi5MM
Description This command set the analog input module channel multiplexing Enabled/Disabled to the specified Slot in the I-8000 system.
Syntax $AASi5MM[CHK](cr)
$ a delimiter character
AA 2-characters HEX module address for the specified I-8000 system ,Range from 01 to FFh
Si Specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
5 command for set the RTD input module channel multiplexing Enabled/Disabled.
MM HEX value .The high nibble must be set to 0.The low nibble byte is mirror to channel 0 to 3.The forth bit is unavailable.
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of command
Response
Valid Command !AA[chk](cr)
Invalid Command ?AA[CHK](cr)
Syntax error or communication error may get no response.
! delimiter for valid command
? delimiter for invalid command
AA 2-characters HEX module address
[CHK] 2-characters of Checksum
(cr) Character Return(0x0D) for denote the end of response
Example
Command $01S0502
Response !01(cr)
Description The hexadecimal 02 equals to binary 0010, the RTD input Module in slot 2 of the I-8000 system at address 01h that set channel multiplexing: channel 1 enabled and channel 0,2,3,4,5,6,7 disabled.
The response indicates the command is valid.





Back to Previous Page