Relay Output Outputs per module 8
Contact Type Form A : normal open (N.O.) contact
Contact Rating 5A@250VAC or 5A@30VDC
Operate/Release Time 6mS/3mS max.
Life Mechanical : 2*107 min.
Electrical : 105 min. (Contact Rating)
Dielectric Strength between open contacts : 750VAC
between coil and contacts : 2000VAC
Surge Strength 4000V
LED Display 1 LED as Power/Communication indicator
8 LEDs as relay output indicators
Power Consumption Maximum : 1.7W


I-87064 Pin Assignment
Terminal Number Pin Name
1 NO0
2 COM0
3 NO1
4 COM1
5 -
6 NO2
7 COM2
8 NO3
9 COM3
10 -
11 NO4
12 COM4
13 NO5
14 COM5
15 -
16 NO6
17 COM6
18 NO7
19 COM7
20 -


I-87064 Block Diagram


Output Type ON State
LED ON
Readback as 1
OFF State
LED OFF
Readback as 0
Relay Contact
Load current On I-87064 Relay Contact
Load current Off I-87064 Relay Contact


I-87064 Dimention


Configuration Default Setting Description
Type 40 Digital Input/Output
Baudrate 0A 115200 bps
Format 00 CheckSum disable


Back to Previous Page