Digital Input Inputs per module 4 (Differential)
Input Type Isolated differential digital input
Input Voltage 30VDC Peak
ON State 3.5VDC Minimum
OFF State 1.0VDC Maximum
Input Impedance 3K Ohms
Isolation Voltage 3750 Vrms
Relay Output Outputs per module 4
Contact Type Form C : changeover contact
Contact Rating 0.6A@125VAC or 2A@30VDC
Operate/Release Time 3mS/2mS max.
Operation Life Mechanical : 108 min.
Electrical : 5*105 min. (2A@30VDC)
Dielectric Strength between open contacts : 500Vrms
between contacts and coil : 1000Vrms
LED Display 1 LED as Power/Communication indicator
4 LEDs as digital input indicators
4 LEDs as relay output indicators
Power Consumption Maximum : 1.0W


I-87063 Pin Assignment
Terminal Number Pin Name
1DI0+
2DI0-
3DI1+
4DI1-
5DI2+
6DI2-
7DI3+
8DI3-
9NO0
10NC0
11COM0
12NO1
13NC1
14COM1
15NO2
16NC2
17COM2
18NO3
19NC3
20COM3


I-87063 Block Diagram


Input Type ON State
LED ON
Readback as 1
OFF State
LED OFF
Readback as 0
Relay Contact
Relay Close I-87063 Digital Input
Relay Open I-87063 Digital Input
TTL/CMOS Logic
Logic Low I-87063 Digital Input
Logic High I-87063 Digital Input
Open Collector
Open Collector On I-87063 Digital Input
Open Collector Off I-87063 Digital Input

Output Type ON State
LED ON
Readback as 1
OFF State
LED OFF
Readback as 0
Relay Contact
Load current On I-87063 Relay Contact
Load current Off I-87063 Relay Contact


I-87063 Dimention


Configuration Default Setting Description
Type 40 Digital Input/Output
Baudrate 0A 115200 bps
Format 00 CheckSum disable


Back to Previous Page