Relay Output Outputs per module
16
Output Type
Power Relay, Form A (SPST N.O.)
Operating Voltage Range
250 VAC/30 VDC
Max. Load Current
10.0 A/per COM point of Module
(at 25 °C).
Max. Single Relay Load Current
5 A at 25 °C
Operate/Release Time
6mS/3mS max.
Mechanical Life 20,000,000 ops. at no load
(300 ops./minute).

Electrical Life (Resistive load)
VDE: 5 A@250 VAC 30,000 ops
(10 ops/minute) at 75°C.
5 A@30 VDC 70,000 ops
(10 ops/minute) at 75°C.
UL: 5 A@250 VAC/30 VDC 6,000 ops.
16 LEDs as relay output indicators3 A@250 VAC/30 VDC 100,000 ops.
LED Display 1 LED as Power/Communication indicator
16 LEDs as relay output indicators
4KV ESD Protection Yes, Contact for each terminal
Power Consumption Maximum : 1.8W












Configuration Default Setting Description
Type 40 Digital Input/Output
Baudrate 0A 115200 bps
Format 00 CheckSum disable