Digital Output Outputs per module 16 (Source)
Output Type Isolated open-collector
Max load current 700mA per channel
Load voltage +10V to +40VDC
Overvoltage Protection 47 VDC
Overload Protection Yes
Short-circuit Protection Yes
Power On Value Yes, Programmable
Safe Value Yes, Programmable
Isolation Voltage 3750 VDC
LED Display 1 LED as Power/Communication indicator
16 LEDs as digital output indicators
4KV ESD Protection Yes, contact for each terminal
Power Consumption Maximum : 0.41W












Configuration Default Setting Description
Type 40 Digital Input/Output
Baudrate 0A 115200 bps
Format 00 CheckSum disable