Analog Output | Output Channel | 2 channels |
Current Output Wiring | Sink | |
Output Type | 0 ~ +10 V 0 ~ +20 mA +4 ~ +20 mA |
|
Accuracy | +/-0.1% of FSR | |
Readback Accuracy | +/-0.5% of FSR | |
Resolution | 12-bit | |
DA Output Responses Time | 10 ms per channel | |
Programmable Output Slope | Voltage: 0.0625 ~ 1024 V/Second |
|
Current: 0.125 ~ 2048 mA/Second | ||
|
Internal Power:500 Ω | |
External Power:1050 Ω | ||
Voltage Output Capability |
10 V @ 10 mA | |
Channel to Channel Isolation | Yes, 3 kV | |
Open Wire Detection | Yes, +4 ~ +20 mA | |
Short Circuit Protection |
Yes |
|
Power-on Value |
Yes |
|
Safe Value |
Yes | |
LED Display | 1 LED
as Power/Communication
indicator |
|
Power Consumption | 1.8 W Max. |
Configuration | Default Setting | Description |
---|---|---|
Type | 2 | 0 ~ 10 V |
Baudrate | 0A | 115200 bps |
Format | 00 | CheckSum disable Immediate Output Engineer Unit Format |
Back to Previous Page |
|